Fire Suppression Strategies for Maintaining Safety, Protecting Critical Equipment

Aug 22, 2024 | Public | 0 comments

Shifting regulations, emerging technologies force many facilities to adjust their hazard fire protection systems.

Fire protection strategies are becoming more complex. New approaches are needed as tried-and-true fire suppression agents are phased out and new hazards are introduced within existing institutional and commercial facilities.

While most buildings rely upon sprinkler systems, certain high-risk facilities demand special hazard protections. Going beyond the basic sprinkler is generally required if water exposure poses a threat to facility equipment.

Suitable fire suppression systems are available for nearly every type of fire risk. Identifying the ideal protection system requires an understanding of facility-specific infrastructure, hazard risks, and occupancy characteristics by facility managers.

Protecting vulnerable equipment

Water-based wet, dry, pre-action and deluge protection systems serve as the best option in many cases to protect buildings and to preserve life. However, the area and assets being protected may experience damage and potential operational outages.

Due to these concerns, special hazard fire protection systems are necessary to safeguard particularly sensitive or valuable assets. Advanced fire-suppression systems are installed to minimize damage in hospitals, data centers, electrical substations, gas turbine generators, and alternative vehicle storage facilities, among other locations.

Hospitals, for example, ensure life safety with systems that can quickly contain flames before a fire reaches patient areas. Suppression systems are also used to protect high-value imaging equipment, information technology rooms, or flammable materials such as oxygen tanks, aesthesia gases, and cleaning products.

Fire suppression solutions range from simple gas extinguishers to complex installations combining various chemical and water-based systems. Options may involve aerosol units, foams, carbon dioxide, or water mist systems. “Clean agent” systems are popular for their ability to extinguish flames by absorbing oxygen from a contained area.

Environmental reforms

Environmental regulations are forcing many facilities to transition to a new generation of fire suppression agents. This is especially true for facilities relying upon clean agent chemicals.

Clean agents flood an entire protected room or compartment with the gas agent — floor-to-ceiling and wall-to-wall — regardless of where within the space the fire is located. Clean agents do not dissipate until the fire event is controlled. Solutions are considered clean agents if they are electrically non-conducting and do not leave behind chemical residues upon evaporation.

Halon was long one of the most popular solutions until, in 1994, the United States banned production and import in alignment with international efforts to phase out ozone-depleting substances (ODS). Signing the international Montreal Protocol on Substances that Deplete the Ozone Layer committed the United States to phase out substances such as Halon.

Since then, several non-toxic ODS alternatives have proven safe for the ozone layer and effective at controlling flames. Yet many have the unintended consequence of contributing significantly to global climate change. The clean agent FM-200, for example, is a popular alternative to Halon. FM-200 is a hydroflurocarbon gas (HFC) with a global warming potential (GWP) more than 3,200 times the potency of carbon dioxide.

The Montreal Protocol was amended in 2016 to discontinue certain carbon-intensive HFCs. In the United States, passage of the 2020 American Innovation and Manufacturing Act (AIM) authorized eventual phasing out of several HFC fire suppression agents. In response to these regulations, manufacturer 3M has instead promoted NOVEC 1230 as an environmentally sustainable replacement for FM-200. The clean agent is not known to deplete the ozone layer and it has a GWP less than carbon dioxide.

Challenges continue: NOVEC 1230 is a polyfluoroalkyl substance (PFAS). Production and disposal of these “forever chemicals” is associated with significant levels of water contamination, among other concerns. In 2022, 3M announced the company will exit PFAS manufacturing and discontinue use of PFAS across their product portfolio by the end of 2025. In doing so, yet another clean agent will become unavailable for purchase.

Fire suppression solutions

Many contractors continue to source and install discontinued suppression systems. Facility owners relying on a discontinued system may face supply shortages and higher replacement costs if the solution discharges. Proactively evaluating fire safety strategies can ensure that an alternative fire suppression agent is on hand whenever disaster strikes.

Carbon dioxide systems offer another alternative. Some local jurisdictions have begun phasing these out as well. The common gas is not considered by the National Fire Protection Association (NFPA) as a clean agent, though it effectively acts as one, removing oxygen while simultaneously working as a cooling agent. Carbon dioxide systems cannot be used within any occupied enclosures due to risks of exposure fatalities.

There is no one-size-fits-all approach when developing a fire protection system. Configurations must be tailored to each building’s layout, occupancy trends, and code requirements — as well as the owner’s operational goals.

Fire protection strategies must conform with the local, state, and federal jurisdiction’s fire safety requirements, NFPA codes, and Occupational Safety and Health Administration (OSHA) standards, as well as insurance underwriter conditions. Other design factors include:

  • Effectiveness: The most important consideration is whether the system provides necessary coverage, while safely addressing the facility’s relevant fire risks. Different suppression systems are needed for electrical fires or flammable and combustible liquid hazards.
  • Structural integrity: Clean agents require an airtight space to prevent gas solution dispersal. Oxygen levels will increase if a room has multiple openings for ductwork, doors, windows, or cabling — complicating efforts to control flames. In these instances, certain clean agents may not be appropriate.
  • Space availability: A clean agent’s tanks must be in a secure area without interference. Otherwise, any accidental damages could have disastrous consequences.
  • Operational controls: Suppression systems can be automated, interacting with early warning smoke, heat and flame detection devices, and coupled with local manual release actuation. Unlike with manual systems, automatic activation and discharge can be aborted if detectors are triggered by mistake.

Many options exist that can reliably and safely address most facilities’ fire hazards. Still, the systems’ design challenges — and alternative solutions’ added costs — can be considerable.

Many owners choose instead to rely upon discontinued suppression agents. Given supply shortages and rising replacement costs, continuing with previous fire protection solutions may eventually backfire. Owners who do not modernize their facility’s fire suppression system do so at their own risk.

By Dimitri Dumerlin and Kenneth Magsam, PE, Contributijng Writers  

Dimitri Dumerlin, LEED AP is a project manager and Kenneth Magsam, PE is a chief mechanical engineer at Burns Engineering, a nationally respected provider of specialized engineering services. 

 




Related Topics:

 

The post "Fire Suppression Strategies for Maintaining Safety, Protecting Critical Equipment" appeared first on Building Operating & Management

0 Comments

Submit a Comment

NFPA Tackles EV Fire Safety for Parking Garages

Alternative fuel vehicles are designed with larger quantities of combustible materials (e.g., fuels, plastics, synthetic...

Door Safety Matters as a Deterrent in School Shootings

  National standards for door security do not exist. Two organizations are trying to change that. Columbine. Sandy...

Five Tune-Ups Your Company Needs in 2025

We combed through MIT SMR’s columns from the past year and culled five tips for leaders who want to recharge their...

Duke University Health System Receives $50 Million for Proton Beam Therapy Center

  An anonymous donor has made a $50 million gift to Duke University Health System toward the development of a proton...

Adaptive Baseball Field Already a Winner in St. Louis

A baseball-related project in St. Louis had better be done right. Baseball is to St. Louis as music is to Nashville or...